意大利:消防安全

对厨房进行消防安全检查以及检查频率。

Checked

本页规则目前为英文版,稍后会翻译成您的语言。

“法律”是指具有约束力的规则。“官方指南”并非法律,但检查人员会参考它。“Chef Hygiene 默认值”是指在没有规则给出具体数值的情况下,应用程序会检查的值。

  • 法律Fire extinguisher checks and maintenance follow the technical standards and the maker’s instructions, and every check is recorded (decree DM 1 September 2021). The technician’s periodic check is every 6 months under standard UNI 9994-1; this is usual practice.
  • 法律The earthing system and any lightning protection are checked every 5 years, or every 2 years in places at higher fire risk. The ASL, ARPA or an authorised body does it (DPR 462/2001, art. 4).
  • 法律Gas boilers for heating or hot water get an efficiency check every 4 years (10–100 kW) or every 2 years (100 kW or more) (DPR 74/2013). No national law sets an interval for gas cooking appliances; a qualified installer fits them and maintenance follows the maker’s instructions.
  • 法律Bars and restaurants do not need a fire prevention certificate. Attached activities do, for example a heat plant over 116 kW (DPR 151/2011).
  • 法律Every employer does a fire risk assessment. An emergency plan is needed with 10 or more workers, or with more than 50 people present at once.