Avstrija: požarna varnost
Preverjanja požarne varnosti vaše kuhinje in kako pogosto jih je treba izvesti.
Checked
Pravila na tej strani so zaenkrat v angleščini. Prevedena bodo v vaš jezik.
»Zakon« je zavezujoče pravilo. »Uradne smernice« niso zakon, vendar jih inšpektorji pričakujejo. »Chef Hygiene privzeto« je vrednost, s katero aplikacija preveri, kadar nobeno pravilo ne določa številke.
- PravoFire extinguishers and fixed extinguishing systems are checked at least every second calendar year, and no more than 27 months apart, by a competent person. Keep the record for 3 years or use a sticker with the test date (AStV § 13).
- PravoEmergency lighting, alarm devices, ventilation and air-conditioning systems and fire alarm systems are checked every year, no more than 15 months apart. Emergency lights and escape signs are checked by eye every month (AStV § 13).
- PravoThe electrical installation is tested by an electrician at most every 5 years. The labour inspectorate can set 3 years for wet or hot areas. The RCD test button is pressed at least every 6 months unless the maker says otherwise (ESV 2012).
- PravoGas checks are set by each federal state’s own gas law, with no national interval. Vienna and Styria set none; others range from 2 to 15 years. A permitted business plant is self-checked every 5 or 6 years (GewO § 82b).
- PravoA fire safety book, fire safety rules and yearly fire drills are required only where the authority has ordered a fire safety officer (AStV §§ 43, 45).
Uradni viri
- Health ministry: hygiene guidelines and Food Code (verbrauchergesundheit.gv.at)
- AGES: food safety, control plan, product warnings
- RIS: Austrian federal and state laws
- Vienna food control (MA 59)
- Labour Inspectorate (workplace safety)
Ta stran je splošna informacija in ne pravni nasvet. Za več informacij se obrnite na lokalne oblasti.