Østrig: brandsikkerhed
Brandsikkerhedstjek for dit køkken, og hvor ofte de skal betales.
Checked
Reglerne på denne side er for nuværende på engelsk. De vil blive oversat til dit sprog.
“Lov” er en bindende regel. “Officiel vejledning” er ikke lov, men inspektører forventer det. “Chef Hygiene standard” er en værdi, som appen kontrollerer i forhold til, hvor ingen regel angiver et tal.
- LovFire extinguishers and fixed extinguishing systems are checked at least every second calendar year, and no more than 27 months apart, by a competent person. Keep the record for 3 years or use a sticker with the test date (AStV § 13).
- LovEmergency lighting, alarm devices, ventilation and air-conditioning systems and fire alarm systems are checked every year, no more than 15 months apart. Emergency lights and escape signs are checked by eye every month (AStV § 13).
- LovThe electrical installation is tested by an electrician at most every 5 years. The labour inspectorate can set 3 years for wet or hot areas. The RCD test button is pressed at least every 6 months unless the maker says otherwise (ESV 2012).
- LovGas checks are set by each federal state’s own gas law, with no national interval. Vienna and Styria set none; others range from 2 to 15 years. A permitted business plant is self-checked every 5 or 6 years (GewO § 82b).
- LovA fire safety book, fire safety rules and yearly fire drills are required only where the authority has ordered a fire safety officer (AStV §§ 43, 45).
Officielle kilder
- Health ministry: hygiene guidelines and Food Code (verbrauchergesundheit.gv.at)
- AGES: food safety, control plan, product warnings
- RIS: Austrian federal and state laws
- Vienna food control (MA 59)
- Labour Inspectorate (workplace safety)
Denne side er til generel information, ikke juridisk rådgivning. Kontakt din kommune.