Luxembourg: fire safety
Fire safety checks for your kitchen, and how often they are due.
Checked
“Law” is a binding rule. “Official guidance” is not law, but inspectors expect it. “Chef Hygiene default” is a value the app checks against where no rule gives a number.
- LawRestaurants for more than 50 people are class 2 classified establishments. The commune gives the permit and sets its own conditions. Where the permit imposes ITM-SST rules 1501.6 or 1502.5, extinguishers must be checked at least every 24 months.
- LawUnder the same ITM-SST rules, safety installations (fire equipment, hood extinguishing, gas detectors, alarm, emergency lights) are checked every year, and electrical installations every 5 years. Hold an evacuation drill every year.
- LawKitchen hoods need automatic extinguishing if the oil reserve is over 100 litres. With 50 to 100 litres, use two 6-litre class F extinguishers or an automatic system. Kitchens also need extinguishers and a fire blanket (ITM-SST 1505.3). No hood cleaning interval was found.
- LawGas boilers, water heaters and stoves over 4 kW need a review every 4 years by an authorised firm (RGD of 27 February 2010). The fire service (CGDIS) advises servicing gas heaters before each winter.
Official sources
- ALVA, food safety in Luxembourg
- Law of 2 April 2026 on food control, Legilux
- HORESCA hygiene guide 2022, ALVA
- Guichet.lu, food safety for businesses
- ITM, fire prevention conditions
This page is general information, not legal advice. Check with your local authority.