Hrvaška: požarna varnost
Preverjanja požarne varnosti vaše kuhinje in kako pogosto jih je treba izvesti.
Checked
Pravila na tej strani so zaenkrat v angleščini. Prevedena bodo v vaš jezik.
»Zakon« je zavezujoče pravilo. »Uradne smernice« niso zakon, vendar jih inšpektorji pričakujejo. »Chef Hygiene privzeto« je vrednost, s katero aplikacija preveri, kadar nobeno pravilo ne določa številke.
- PravoThe owner checks each extinguisher at least every 3 months and records it. An authorised firm services it at least every year and after any use (Rulebook NN 101/11). Each floor needs at least 2 extinguishers (Rulebook NN 100/99).
- PravoVentilation ducts from food-preparation rooms are cleaned every 3 months while the premises are open. Other ventilation ducts are cleaned at least yearly, with a written record (Rulebook NN 100/99, Art. 27).
- PravoEmergency lighting is checked twice a year, once just before the main season, and recorded (Rulebook NN 100/99, Art. 23). Small ground-floor food premises are excepted.
- PravoThe electrical installation is inspected and measured at least every 4 years. Keep the written report (technical regulation NN 5/2010).
Uradni viri
- State Inspectorate (Državni inspektorat)
- Croatian Chamber of Trades and Crafts (HOK), catering HACCP guide
- HACCP rulebook NN 124/2025
- Food hygiene Act NN 83/22
Ta stran je splošna informacija in ne pravni nasvet. Za več informacij se obrnite na lokalne oblasti.